PRODUCTS
Electronic
Equipment |
|
NC-WATCH |
|
 |
The NC-WATCH family unit offers remote
control capability for power network and capacitor banks. The control
connection to NC-WATCH solution can be made using LAN or GSM connection.
NC-WATCH solution controls the operation of
the power factor controller. The most important values, which describe
the status of power grid, are read from the power factor controller.
Additionally, alarm events on the controller and communication to the
controller can be monitored. NC-WATCH offers a web page for each PFC.
The web pages can be read via a LAN in addition to the Internet. The web
pages have the current values of the power network status and one
selectable trend curve. With an external GSM modem the status of the
power network can be received by an SMS message.
NC-Watch (.pdf) |
|
POWER FACTOR CONTROLLERS N-6, N-12 AND NC-12 |
|

 |
Power factor
controllers models for 6 or 12 steps are designed and manufactured to control automatic capacitor
banks. They provide your network with efficient reactive power
compensation, measuring, supervision and communication features. They
are modular, robust, compact, programmable and easy to install and to
use.
Power factor controllers (.pdf) |
|
UNBALANCE CURRENT PROTECTION RELAY NUR-36 |
|
 |
Protective relay NUR-36 is a
single phase, sensitive, over-current relay. It features two stages of
over-current protection, both having their own parameters and output
relays. The NUR-36 is designed for unbalance current protection of
double-star (Y-Y) connected capacitor banks in high voltage
applications. It has solid state construction and is suitable for panel
installation (DIN 43700). The relay has filters for harmonic currents
and operate at fundamental frequency only. Protection is tested
according to IEC 255-5c, 255-22-2 class III, 801-4 class III and the
product fulfils the CE requirements. Information about measurements and
relay functions is given by digital display and LED's.
Protection relay NUR-36 (.pdf) |
|
CAPACITANCE METER NCM-20 |
|
 |
Capacitance Meter type NCM-20 is
designed to measure capacitor units in a capacitor bank without removing
any connecting wire between separate capacitor units. This measurement
is used to locate blown fuses in the units. NCM-20 is battery operated
and portable comprising a separate display and generator untis and is
well suited for field use. The measured capacitance is displayed by a 3
½-digit LCD-display on the display unit. The generator unit includes a
built-in calibration capacitor.
Capacitance meter NCM-20 (.pdf) |
|